Camp Far West Irrigation District — Daily Water Report

North Canal Diversion · Picovale Device M007949 · Report date: Monday, July 20, 2026
North Ditch Gate
10.5″
Set 6/24, 05:18 (unchanged)
Latest Meter Reading
9.31 cfs
Jul 20, 08:00 (Picovale) · 24-h avg ~8.8
Active Orders
8 cfs
AKT 8 + Bear River 0

1. Meter Flow, Water Orders & Gate Setting — Past Week

Hourly Picovale flow and total active water orders (left axis, cfs) plotted against the North Ditch gate setting (right axis, inches), Jul 14 – Jul 20:

04812162024cfsgate″cfs (calib.)012345678910111220.2±0.99.6±0.415.1±0.622.8±1.013.2±0.60.9±0.32.9±0.17.7±0.413.7±0.114.6±0.718.8±4.81.94.715.821.424.2cfs ≈ 2.8×in -9.2bold=measured, italic=fitJul 14Jul 15Jul 16Jul 17Jul 18Jul 19Jul 20Picovale meter (cfs)Water orders (cfs)Gate setting (in)

2. North Ditch Gate Setting

DateTimeGate (in)ChangeSet by
2026-06-2405:1810.5Raised from 8.5″ currentHenry
2026-06-2209:358.5Raised from 8.1″Henry
2026-06-2205:348.1Raised from 7″Henry
2026-06-2010:157Raised from 6.1″Henry
2026-06-2005:326.1Raised from -1″Henry

3. Water Orders

SourceCFSEffective startEffective endNotes
AKT82026-07-12 07:002026-07-21 07:00Stands until changed
Bear River02026-07-17 07:002026-07-21 07:00Stands until changed
Bear River82026-07-21 07:00ongoingStands until changed
AKT182026-07-21 07:00ongoingStands until changed

Current standing orders total 8 cfs. Orders are due 24 h ahead of a 7am delivery.

4. Picovale Meter Level

At an unchanged 10.5″ gate, flow is holding near 8.8 cfs (24-h average), running about 0.8 cfs over the 8 cfs order. Selected hourly readings (full series in master.csv):

DateTimecfsDiverted (AF)Note
2026-07-2003:008.740.722
2026-07-2004:008.470.700
2026-07-2005:008.470.700
2026-07-2006:009.020.745
2026-07-2007:009.310.769
2026-07-2008:009.310.769Latest latest

Prior full day (7/19) diverted 17.5 AF over 24 hours.

5. Gate → Meter Response

The gate is at 10.5″ (set 6/24). Recent daily-average flow: 24.6 (7/16), 14.3 (7/17), 8.9 (7/18), 8.8 (7/19), 8.9 (7/20). The 24-h mean is 8.8 cfs with scatter min 8.2, max 9.3, SD 0.3 — supply is running about 0.8 cfs over the 8 cfs order.

Calibration: at the current 10.5″ the rating point is 10.5″ → 18.8 cfs (n=612). Fit: cfs ≈ 2.8×in -9.2, so 8 cfs → ~6.2″. The website gate calculator uses this regression.

6. Weekly Shareholder Notes

Space reserved for weekly notes to shareholders — announcements, reminders, or items for the next meeting. (Add notes here before publishing.)